Rosslare AC-225? AC-225IP? AC-225U Guia do Utilizador Página 22

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 45
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 21
Input and Output Requirements
Normally Closed Supervised Single Resistor Input Connection
Connect a 2.2K resistor in series to the input switch contacts.
Normally Closed Supervised Input has 3 states:
Switch Closed - Normal State:
Loop resistance = 2.2K.
Switch Open – Abnormal State:
Loop resistance = Infinite (open circuit).
Short circuit across input terminals - Trouble State:
Loop resistance = 0 (short circuit).
Figure 12: Normally Closed Supervised Input (Single Resistor)
Normally Closed Supervised Double Resistor Input Connection
Connect a 2.2K resistor in series to the input switch contacts.
Connect an 8.2K resistor parallel to the input switch contacts.
Normally Closed Supervised Input has 3 states:
Switch Closed - Normal State:
Loop resistance = 2.2K.
Switch Open – Abnormal State:
Loop resistance = 10.4K.
AC-225 Hardware Installation and User Guide Page 21
Vista de página 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 44 45

Comentários a estes Manuais

Sem comentários