13
Figure 3.5-6 Setting panel of the Door object
2. From the Number dropdown list select the door address (Figure 3.5-6, 1).
3. From the Authorize re-closing dropdown list select the door-closing mode (Table 3.5-1, Figure
3.5-6, 2).
Table 3.5-1 Description of door operation mode
Operation mode
Description of operation mode
No
Lock opens for programmed period
Door monitoring is closed
Lock timer stops after door-closing
Door monitoring is open
Lock timer stops after door-opening
4. To enable the exit button set the Exit button enabled checkbox. (Figure 3.5-6, 3).
5. To enable the automatic door opening after the first incoming user set the First employee
opens automatically checkbox (Figure 3.5-6, 4).
6. To activate the exit mode set the Door-exit opposition ‘normally closed’ checkbox (Figure 3.5-6,
5).
7. In the Open by timer field using up-down keys set the time (in minutes and seconds) at the
expiration of which the door opens (Figure 3.5-6, 6).
8. In the Door-opening time field using up-down keys set the time (in minutes and seconds)
during which the lock is open (Figure 3.5-6, 7).
9. In the Extra door-opening time field using up-down keys set the extra time period (in minutes
and seconds) during which the door may be open (Figure 3.5-6, 8).
10. Set the Door left open checkbox and using up-down keys set the time (in minutes and seconds)
during which the door may be open (Figure 3.5-6, 9).
11. Set the Door hacked checkbox and using up-down keys set the time (in minutes and seconds) at
the expiration of which the door is considered to be hacked (Figure 3.5-6, 10).
12. To save changes click Apply (Figure 3.5-6, 11).